INPUT .. $ --------------------------------------------------------- $ Abort, Diagnostics $ --------------------------------------------------------- $ --------------------------------------------------------- $ Global Parameters $ --------------------------------------------------------- PARAMETER "Attic Roof U" = 0.0167 .. PARAMETER "Green Roof U" = 0.0167 .. PARAMETER "ECB Fixed Win U" = 0.155 .. PARAMETER "ECB Csmt Win U" = 0.205 .. PARAMETER "S Off Win TF OH Length" = 4 .. PARAMETER "S Off Win GF OH Length" = 5 .. PARAMETER "ECB Opaque Door U" = 0.086 .. PARAMETER "Int Slab Ins k" = 0.0192 .. PARAMETER "Office Wall U" = 0.026 .. PARAMETER "Lab Wall U" = 0.026 .. PARAMETER "Bsmt Wall Ins R" = 9 .. PARAMETER "Ins Conc Form R" = 12.5 .. PARAMETER "DayLgtPwrFrac" = 0.3 .. PARAMETER "DayLgtLgtFrac" = 0.2 .. $ --------------------------------------------------------- $ Title, Run Periods, Design Days, Holidays $ --------------------------------------------------------- TITLE LINE-1 = *101 - RTF Real* LINE-2 = *Natural Ventilation/Cooling* LINE-3 = *Modeler: Don Cott; don.cott@ak.net* LINE-4 = *http://home.gci.net/~tse/* .. "Full Year" = RUN-PERIOD-PD BEGIN-YEAR = 2007 .. "Standard US Holidays" = HOLIDAYS LIBRARY-ENTRY "US" .. $ --------------------------------------------------------- $ Compliance Data $ --------------------------------------------------------- $ --------------------------------------------------------- $ Site and Building Data $ --------------------------------------------------------- "Site Data" = SITE-PARAMETERS ALTITUDE = 436 .. "Building Data" = BUILD-PARAMETERS HOLIDAYS = "Standard US Holidays" .. $ --------------------------------------------------------- $ Materials / Layers / Constructions $ --------------------------------------------------------- "EPS 2in (R4.5/in)" = MATERIAL TYPE = RESISTANCE RESISTANCE = {parameter("Bsmt Wall Ins R")} .. "FG 3.5in batt wood studs 16inoc" = MATERIAL TYPE = RESISTANCE RESISTANCE = 11 .. "Polystyrene 6in R-4.5/in" = MATERIAL TYPE = RESISTANCE RESISTANCE = 27 .. "3.5in FG Batt 16in steel oc" = MATERIAL TYPE = RESISTANCE RESISTANCE = 9 .. "Blown-in Cellulose" = MATERIAL TYPE = PROPERTIES THICKNESS = 1 CONDUCTIVITY = 0.026 DENSITY = 3 SPECIFIC-HEAT = 0.33 .. "HiDen 2in Variable EPS" = MATERIAL TYPE = PROPERTIES THICKNESS = 0.167 CONDUCTIVITY = {parameter("Int Slab Ins k")} DENSITY = 2 SPECIFIC-HEAT = 0.29 .. "HiDen Invarient 2in EPS" = MATERIAL TYPE = PROPERTIES THICKNESS = 0.167 CONDUCTIVITY = 0.0192 DENSITY = 2 SPECIFIC-HEAT = 0.29 .. "Ins. Conc. Form" = MATERIAL TYPE = RESISTANCE RESISTANCE = {parameter("Ins Conc Form R")} .. "Ext Lab Wall Lay" = LAYERS MATERIAL = ( "Stucco 1in (SC01)", "Polystyrene 6in R-4.5/in", "Plywd 5/8in (PW04)", "3.5in FG Batt 16in steel oc", "Air Lay <4in Vert (AL21)", "GypBd 5/8in (GP02)" ) THICKNESS = ( 0.021 ) .. "Green Roof Lay" = LAYERS MATERIAL = ( "Light Soil, Damp 12in", "Blt-Up Roof 3/8in (BR01)", "Polystyrene 6in R-4.5/in", "Polystyrene 6in R-4.5/in", "Steel Siding (HF-A3)" ) THICKNESS = ( 0.33, &D, &D, &D, 0.0075 ) .. "Slab Interior Lay" = LAYERS MATERIAL = ( "HiDen 2in Variable EPS", "HiDen 2in Variable EPS", "Conc HW 140lb 12in (HF-C11)" ) THICKNESS = ( 0.167, &D, 0.67 ) .. "Off Ext Wall Lay" = LAYERS MATERIAL = ( "Stucco 1in (SC01)", "EPS 2in (R4.5/in)", "EPS 2in (R4.5/in)", "EPS 2in (R4.5/in)", "Plywd 5/8in (PW04)", "FG 3.5in batt wood studs 16inoc", "Air Lay >4in Horiz (AL33)", "GypBd 5/8in (GP02)" ) THICKNESS = ( 0.0208 ) .. "Off Int Flr Lay" = LAYERS MATERIAL = ( "Wood 2in (HF-B10)", "Conc LW 30lb 3in", "Carpet & No Pad" ) THICKNESS = ( 0.167 ) .. "Bsmt Wall Lay" = LAYERS MATERIAL = ( "HiDen Invarient 2in EPS", "Ins. Conc. Form", "Conc HW 140lb 12in (HF-C11)", "Ins. Conc. Form", "Air Lay <4in Vert (AL21)", "GypBd 5/8in (GP02)" ) THICKNESS = ( 0.1025, 0.23, 0.67 ) .. "IWall Cons Layers" = LAYERS MATERIAL = ( "GypBd 5/8in (GP02)", "Air Lay <4in Vert (AL21)", "GypBd 5/8in (GP02)" ) THICKNESS = ( 0.052 ) .. "EWall Cons Layers" = LAYERS MATERIAL = ( "Stucco 1in (SC01)", "EPS 2in (R4.5/in)", "Plywd 1/2in (PW03)", "Air Lay >4in Horiz (AL33)", "GypBd 1/2in (GP01)" ) THICKNESS = ( 0.25, 0.5, &D, 0.458, 0.052 ) .. "Blown-In Roof Lay" = LAYERS MATERIAL = ( "Blown-in Cellulose", "GypBd 5/8in (GP02)" ) THICKNESS = ( 1.6 ) .. "Ceiling Lay" = LAYERS MATERIAL = ( "AcousTile 3/4in (AC03)" ) THICKNESS = ( 0.06 ) .. "Perimeter Slab Lay" = LAYERS MATERIAL = ( "HiDen 2in Variable EPS", "HiDen 2in Variable EPS", "Conc HW 140lb 12in (HF-C11)" ) THICKNESS = ( &D, &D, 0.67 ) .. "Interior Slab Lay" = LAYERS MATERIAL = ( "HiDen 2in Variable EPS", "HiDen 2in Variable EPS", "Conc HW 140lb 12in (HF-C11)" ) THICKNESS = ( &D, &D, 0.67 ) .. "Slab Perimeter Lay" = LAYERS MATERIAL = ( "HiDen 2in Variable EPS", "HiDen Invarient 2in EPS", "Conc HW 140lb 12in (HF-C11)" ) THICKNESS = ( &D, &D, 0.67 ) .. "Lab Wall Con" = CONSTRUCTION TYPE = U-VALUE ABSORPTANCE = 0.6 ROUGHNESS = 1 U-VALUE = {parameter("Lab Wall U")} .. "Green Lab Roof Con" = CONSTRUCTION TYPE = U-VALUE ABSORPTANCE = 0.6 ROUGHNESS = 1 U-VALUE = {parameter("Green Roof U")} .. "Ceilg Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "Ceiling Lay" .. "Slab Interior Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "Slab Interior Lay" .. "Off Wall Con" = CONSTRUCTION TYPE = U-VALUE ABSORPTANCE = 0.84 ROUGHNESS = 4 U-VALUE = {parameter("Office Wall U")} .. "Blown-In Roof Con" = CONSTRUCTION TYPE = U-VALUE ABSORPTANCE = 0.51 ROUGHNESS = 2 U-VALUE = {parameter("Attic Roof U")} .. "Int Hydron Flr Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "Off Int Flr Lay" .. "Bsmt Wall Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "Bsmt Wall Lay" .. "Opaque Door Con" = CONSTRUCTION TYPE = U-VALUE U-VALUE = {parameter("ECB Opaque Door U")} .. "Int Wall Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "IWall Cons Layers" .. "Slab Perimeter Con" = CONSTRUCTION TYPE = LAYERS LAYERS = "Slab Perimeter Lay" .. $ --------------------------------------------------------- $ Glass Type Codes $ --------------------------------------------------------- $ --------------------------------------------------------- $ Glass Types $ --------------------------------------------------------- "Northerm 3255 Fixed Win" = GLASS-TYPE TYPE = SHADING-COEF SHADING-COEF = 0.6 GLASS-CONDUCT = {parameter("ECB Fixed Win U")} VIS-TRANS = 0.455 OUTSIDE-EMISS = 0.036 .. "Northerm 3255 Casement Win" = GLASS-TYPE TYPE = SHADING-COEF SHADING-COEF = 0.6 GLASS-CONDUCT = {parameter("ECB Csmt Win U")} VIS-TRANS = 0.34 OUTSIDE-EMISS = 0.036 .. $ --------------------------------------------------------- $ Window Layers $ --------------------------------------------------------- $ --------------------------------------------------------- $ Lamps / Luminaries / Lighting Systems $ --------------------------------------------------------- $ --------------------------------------------------------- $ Day Schedules $ --------------------------------------------------------- "Bsmt Area Lighting WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05, &D, &D, &D, &D, &D, 0.05, 0.05, 0.05, &D, &D, 0.05, &D, 0.9, &D, 0.05, 0.05, 0.05, 0.05, &D, &D, &D, 0.05 ) .. "Office Area Lighting WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05, &D, &D, &D, &D, &D, 0.2965, 0.798, 0.9, &D, &D, &D, &D, &D, &D, &D, 0.798, 0.5005, 0.2965, &D, 0.101, &D, 0.05 ) .. "Off Bldg OffEq WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.12, &D, &D, &D, &D, &D, 0.2214, 0.7596, 0.9, &D, &D, 0.7362, &D, 0.9, &D, &D, 0.822, 0.4164, 0.2214, &D, 0.159, &D, 0.12 ) .. "Off Bldg OffEq WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.036 ) .. "Off Bldg OffEq HDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0 ) .. "Off Bldg OffEq CDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.12, &D, &D, &D, &D, &D, 0.2214, 0.7596, 0.9, &D, &D, 0.7362, &D, 0.9, &D, &D, 0.822, 0.4164, 0.2214, &D, 0.159, &D, 0.12 ) .. "Off Bldg Misc WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.2, &D, &D, &D, &D, &D, 0.298, 0.802, 0.9, &D, &D, &D, &D, &D, &D, &D, &D, 0.501, 0.298, &D, 0.2 ) .. "Off Bldg Misc WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.06 ) .. "Off Bldg Misc HDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0 ) .. "Off Bldg Misc CDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.2, &D, &D, &D, &D, &D, 0.298, 0.802, 0.9, &D, &D, &D, &D, &D, &D, &D, &D, 0.501, 0.298, &D, 0.2 ) .. "DHW Eqp NRes WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05, &D, &D, &D, &D, &D, 0.101, 0.5005, &D, 0.9, &D, &D, &D, &D, &D, 0.696, 0.5005, 0.2965, 0.203, &D, &D, 0.05 ) .. "DHW Eqp NRes WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.015 ) .. "DHW Eqp NRes HDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0 ) .. "DHW Eqp NRes CDD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05, &D, &D, &D, &D, &D, 0.101, 0.5005, &D, 0.9, &D, &D, &D, &D, &D, 0.696, 0.5005, 0.2965, 0.203, &D, &D, 0.05 ) .. "All Fans WD" = DAY-SCHEDULE-PD TYPE = ON/OFF/FLAG VALUES = ( -999, &D, &D, &D, &D, &D, 0, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, -999 ) .. "All Fans WEH" = DAY-SCHEDULE-PD TYPE = ON/OFF/FLAG VALUES = ( -999, &D, &D, &D, &D, &D, &D, &D, -999, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999 ) .. "Up Off Zns Cooling WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120, &D, &D, &D, &D, &D, &D, 120, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 120 ) .. "Up Off Zns Cooling WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120 ) .. "Up Off Zns Heating WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66, &D, &D, &D, &D, &D, &D, 66, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 66 ) .. "Up Off Zns Heating WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "Bsmt Area Lighting WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05, &D, &D, &D, &D, &D, 0.05, 0.05, 0.05, &D, &D, 0.05, &D, 0.2, &D, 0.05, 0.05, 0.05, 0.05, &D, &D, &D, 0.05 ) .. "Office Area Lighting WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0.05 ) .. "Bsmt Cooling WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120, &D, &D, &D, &D, &D, &D, 120, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 120 ) .. "Bsmt Heating WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66, &D, &D, &D, &D, &D, &D, 66, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 66 ) .. "Bsmt Heating WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "Bsmt Cooling WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120 ) .. "Bsmt Occup WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Bsmt Occup WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 0, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Grd Fl Occup WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Grd Fl Occup WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Top Fl Occup WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Top Fl Occup WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "IT Rm Heat Otpt Sch" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 1 ) .. "N Lab Htg WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66, &D, &D, &D, &D, &D, &D, 66, &D, &D, &D, &D, &D, &D, &D, &D, 66 ) .. "S Lab Htg WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66, &D, &D, &D, &D, &D, &D, 66, &D, &D, &D, &D, &D, &D, &D, &D, 66 ) .. "El Sh Htg WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "TF HW Summer" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 0 ) .. "Atr Htg WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "El Sh Clg WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120 ) .. "Clg off Day" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 0 ) .. "Clg on Day" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 1 ) .. "Htg on Day" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 1 ) .. "Htg off Day" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 0 ) .. "Fan Htg/Clg to SP Day" = DAY-SCHEDULE-PD TYPE = ON/OFF/FLAG VALUES = ( -999 ) .. "S Lab Clg Day" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120 ) .. "N Lab Clg Day" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 120 ) .. "N Lab Htg WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "S Lab Htg WEH" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 66 ) .. "Nat Vent Temp Desired WD" = DAY-SCHEDULE-PD TYPE = TEMPERATURE VALUES = ( 70 ) .. "Nat Vent Sch WD" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 0, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) .. "Nat Vent Sch WEH" = DAY-SCHEDULE-PD TYPE = ON/OFF VALUES = ( 0 ) .. "Win Open Prob WD" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0, &D, &D, &D, &D, &D, &D, 0.3, 0.6, 1, &D, &D, &D, &D, &D, &D, &D, 0.3, 0 ) .. "Win Open Prob WEH" = DAY-SCHEDULE-PD TYPE = FRACTION VALUES = ( 0 ) .. "Fan Summer Shutdown Day" = DAY-SCHEDULE-PD TYPE = ON/OFF/FLAG VALUES = ( -1 ) .. $ --------------------------------------------------------- $ Week Schedules $ --------------------------------------------------------- "Off Bldg OffEq Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Off Bldg OffEq WD", &D, &D, &D, &D, "Off Bldg OffEq WEH", &D, &D, "Off Bldg OffEq HDD", "Off Bldg OffEq CDD" ) .. "Off Bldg Misc Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Off Bldg Misc WD", &D, &D, &D, &D, "Off Bldg Misc WEH", &D, &D, "Off Bldg Misc HDD", "Off Bldg Misc CDD" ) .. "DHW Eqp NRes Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "DHW Eqp NRes WD", &D, &D, &D, &D, "DHW Eqp NRes WEH", &D, &D, "DHW Eqp NRes HDD", "DHW Eqp NRes CDD" ) .. "All Fans Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF/FLAG DAY-SCHEDULES = ( "All Fans WD", &D, &D, &D, &D, "All Fans WEH" ) .. "Up Off Zns Cooling Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Up Off Zns Cooling WD", &D, &D, &D, &D, "Up Off Zns Cooling WEH" ) .. "Up Off Zns Heating Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Up Off Zns Heating WD", &D, &D, &D, &D, "Up Off Zns Heating WD" ) .. "Office Area Lighting Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Office Area Lighting WD", &D, &D, &D, &D, "Office Area Lighting WEH" ) .. "Bsmt Area Lighting WK" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Bsmt Area Lighting WD", &D, &D, &D, &D, "Bsmt Area Lighting WEH" ) .. "Bsmt Cooling Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Bsmt Cooling WD", &D, &D, &D, &D, "Bsmt Cooling WEH" ) .. "Bsmt Heating Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Bsmt Heating WD", &D, &D, &D, &D, "Bsmt Heating WEH" ) .. "Bsmt Occup Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Bsmt Occup WD", &D, &D, &D, &D, "Bsmt Occup WEH" ) .. "Grd Fl Occup Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Grd Fl Occup WD", &D, &D, &D, &D, "Grd Fl Occup WEH" ) .. "Top Fl Occup Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Top Fl Occup WD", &D, &D, &D, &D, "Top Fl Occup WEH" ) .. "IT Rm Heat Output Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "IT Rm Heat Otpt Sch" ) .. "N Lab Htg WK" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "N Lab Htg WD", &D, &D, &D, &D, "N Lab Htg WEH" ) .. "S Lab Htg Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "S Lab Htg WD", &D, &D, &D, &D, "S Lab Htg WEH" ) .. "El Sh Htg Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "El Sh Htg WD", &D, "El Sh Htg WD", "El Sh Htg WD", "El Sh Htg WD", "El Sh Htg WD", "El Sh Htg WD", "S Lab Htg WD", "S Lab Htg WD", "S Lab Htg WD" ) .. "Atr Htg WK" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Atr Htg WD", &D, &D, &D, &D, "Atr Htg WD" ) .. "El Sh Clg Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "El Sh Clg WD", &D, &D, &D, &D, "El Sh Clg WD" ) .. "Clg on Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF DAY-SCHEDULES = ( "Clg on Day", &D, &D, &D, &D, "Clg on Day" ) .. "Htg on Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF DAY-SCHEDULES = ( "Htg on Day", &D, &D, &D, &D, "Htg on Day" ) .. "Htg off Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF DAY-SCHEDULES = ( "Htg off Day", &D, &D, &D, &D, "Htg off Day" ) .. "Clg off Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF DAY-SCHEDULES = ( "Clg off Day", &D, &D, &D, &D, "Clg off Day" ) .. "Fan Htg/Clg to SP Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF/FLAG DAY-SCHEDULES = ( "Fan Htg/Clg to SP Day", &D, &D, &D, &D, "Fan Htg/Clg to SP Day" ) .. "S Lab Clg Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "S Lab Clg Day", &D, &D, &D, &D, "S Lab Clg Day" ) .. "N Lab Clg Wk" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "N Lab Clg Day", &D, &D, &D, &D, "N Lab Clg Day" ) .. "Nat Vent Temp Desired WK" = WEEK-SCHEDULE-PD TYPE = TEMPERATURE DAY-SCHEDULES = ( "Nat Vent Temp Desired WD", &D, &D, &D, &D, "Nat Vent Temp Desired WD" ) .. "Nat Vent Sch Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF DAY-SCHEDULES = ( "Nat Vent Sch WD", &D, &D, &D, &D, "Nat Vent Sch WEH" ) .. "Win Open Prob Wk" = WEEK-SCHEDULE-PD TYPE = FRACTION DAY-SCHEDULES = ( "Win Open Prob WD", &D, &D, &D, &D, "Win Open Prob WEH" ) .. "Fan Summer Shutdown Wk" = WEEK-SCHEDULE-PD TYPE = ON/OFF/FLAG DAY-SCHEDULES = ( "Fan Summer Shutdown Day", &D, &D, &D, &D, "Fan Summer Shutdown Day" ) .. $ --------------------------------------------------------- $ Annual Schedules $ --------------------------------------------------------- "Off Bldg OffEq Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Off Bldg OffEq Wk" ) .. "Off Bldg Misc Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Off Bldg Misc Wk" ) .. "DHW Eqp NRes Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "DHW Eqp NRes Wk" ) .. "All Fans Sch" = SCHEDULE-PD TYPE = ON/OFF/FLAG MONTH = ( 5, 9, 12 ) DAY = ( 16, 15, 31 ) WEEK-SCHEDULES = ( "All Fans Wk", "Fan Summer Shutdown Wk", "All Fans Wk" ) .. "Up Off Zns Cooling Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Up Off Zns Cooling Wk" ) .. "Up Off Zns Heating Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Up Off Zns Heating Wk" ) .. "Office Area Lighting Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Office Area Lighting Wk" ) .. "Bsmt Area Lighting Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Area Lighting WK" ) .. "Bsmt Cooling Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Cooling Wk" ) .. "Bsmt Heating Sch" = SCHEDULE-PD TYPE = TEMPERATURE GROUP = ZONE-LOADS MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Heating Wk" ) .. "Bsmt Occup Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "Grd Fl Occup Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Grd Fl Occup Wk" ) .. "Top Fl Occup Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Top Fl Occup Wk" ) .. "Elev Occ Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "At GF Occ Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "Atrium Occupancy Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "Atr Bsmt Occ Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "Atr Bsmt Eq Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Off Bldg OffEq Wk" ) .. "Atr Grd Fl Occ Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Grd Fl Occup Wk" ) .. "S Lab Occ" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "S Lab Eq Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Off Bldg OffEq Wk" ) .. "S Lab Inf Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Week Schedule FRACTION" ) .. "S Lab Ltg" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Area Lighting WK" ) .. "N Lab Occ Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Occup Wk" ) .. "N Lab Eq Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Off Bldg OffEq Wk" ) .. "N Lab Inf Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Week Schedule FRACTION" ) .. "N Lab Lgt Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Bsmt Area Lighting WK" ) .. "IT Rm Heat Output Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "IT Rm Heat Output Wk" ) .. "N Lab Htg Sch" = SCHEDULE-PD TYPE = TEMPERATURE GROUP = ZONE-LOADS MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "N Lab Htg WK" ) .. "S Lab Htg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "S Lab Htg Wk" ) .. "El Sh Htg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "El Sh Htg Wk" ) .. "Seasonal Htg Sch" = SCHEDULE-PD TYPE = ON/OFF MONTH = ( 5, 9, 12 ) DAY = ( 15, 15, 31 ) WEEK-SCHEDULES = ( "Htg on Wk", "Htg off Wk", "Htg on Wk" ) .. "Seasonal Clg Sch" = SCHEDULE-PD TYPE = ON/OFF MONTH = ( 5, 10, 12 ) DAY = ( 1, 30, 31 ) WEEK-SCHEDULES = ( "Clg off Wk", "Clg off Wk", "Clg off Wk" ) .. "Atr Htg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Atr Htg WK" ) .. "El Sh Clg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "El Sh Clg Wk" ) .. "Fan Htg/Clg to SP Sch" = SCHEDULE-PD TYPE = ON/OFF/FLAG MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Fan Htg/Clg to SP Wk" ) .. "S Lab Clg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "S Lab Clg Wk" ) .. "N Lab Clg Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "N Lab Clg Wk" ) .. "Nat Vent Desired Temp Sch" = SCHEDULE-PD TYPE = TEMPERATURE MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Nat Vent Temp Desired WK" ) .. "Nat Vent Sch" = SCHEDULE-PD TYPE = ON/OFF MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Nat Vent Sch Wk" ) .. "Win Open Prob Sch" = SCHEDULE-PD TYPE = FRACTION MONTH = ( 12 ) DAY = ( 31 ) WEEK-SCHEDULES = ( "Win Open Prob Wk" ) .. $ --------------------------------------------------------- $ Polygons $ --------------------------------------------------------- "Off Floor Polygon" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 42 ) V4 = ( 0, 42 ) .. "Off Roof Polygon 1 Wall 1" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 42 ) V4 = ( 0, 42 ) .. "Off Floor Polygon - SMirro" = POLYGON V1 = ( 0, 0 ) V2 = ( 42, 0 ) V3 = ( 42, 48 ) V4 = ( 0, 48 ) .. "Off Bsmt Int Slab Poly - Mirro" = POLYGON V1 = ( 2, 2 ) V2 = ( 40, 2 ) V3 = ( 40, 46 ) V4 = ( 2, 46 ) .. "Off Bsmt E Per Slab Poly - Mirro" = POLYGON V1 = ( 0, 0 ) V2 = ( 42, 0 ) V3 = ( 40, 2 ) V4 = ( 2, 2 ) .. "Off Bsmt N Per Slab Poly - Mirro" = POLYGON V1 = ( 0, 0 ) V2 = ( 2, 2 ) V3 = ( 2, 46 ) V4 = ( 0, 48 ) .. "Off Bsmt S Per Slab Poly - Mirro" = POLYGON V1 = ( 42, 0 ) V2 = ( 42, 48 ) V3 = ( 40, 46 ) V4 = ( 40, 2 ) .. "Off Bsmt W Per Slab S Poly - Mir" = POLYGON V1 = ( 42, 48 ) V2 = ( 32, 48 ) V3 = ( 32, 46 ) V4 = ( 40, 46 ) .. "Off Bsmt W Per Slab N Poly - Mir" = POLYGON V1 = ( 0, 48 ) V2 = ( 2, 46 ) V3 = ( 10, 46 ) V4 = ( 10, 48 ) .. "Off Bsmt W Int Slab C Poly - Mir" = POLYGON V1 = ( 10, 48 ) V2 = ( 10, 46 ) V3 = ( 32, 46 ) V4 = ( 32, 48 ) .. "Atr Main Flr Plan Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, -6 ) V4 = ( 62, -6 ) V5 = ( 62, 10 ) V6 = ( 55, 10 ) V7 = ( 55, 20 ) V8 = ( 48, 20 ) V9 = ( 48, 14 ) V10 = ( 0, 14 ) .. "Atr Main Flr Plan Poly - Mirro" = POLYGON V1 = ( 0, 14 ) V2 = ( 0, 0 ) V3 = ( 48, 0 ) V4 = ( 48, -6 ) V5 = ( 55, -6 ) V6 = ( 55, 4 ) V7 = ( 62, 4 ) V8 = ( 62, 20 ) V9 = ( 48, 20 ) V10 = ( 48, 14 ) .. "Atr Interior Slab Poly" = POLYGON V1 = ( 2, 0 ) V2 = ( 48, 0 ) V3 = ( 48, -4 ) V4 = ( 62, -4 ) V5 = ( 62, 10 ) V6 = ( 55, 10 ) V7 = ( 55, 18 ) V8 = ( 48, 18 ) V9 = ( 48, 14 ) V10 = ( 2, 14 ) .. "Atr Bsmt W Per Slab Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 2, 0 ) V3 = ( 2, 14 ) V4 = ( 0, 14 ) .. "Atr Bsmt N Per Slab Poly" = POLYGON V1 = ( 48, 18 ) V2 = ( 55, 18 ) V3 = ( 55, 20 ) V4 = ( 48, 20 ) .. "Atr Bsmt S Per Slab Poly" = POLYGON V1 = ( 48, -6 ) V2 = ( 62, -6 ) V3 = ( 62, -4 ) V4 = ( 48, -4 ) .. "Elev Flr Plan Poly" = POLYGON V1 = ( 55, 10 ) V2 = ( 62, 10 ) V3 = ( 62, 20 ) V4 = ( 55, 20 ) .. "Elev Int Slab Poly" = POLYGON V1 = ( 55, 10 ) V2 = ( 62, 10 ) V3 = ( 62, 18 ) V4 = ( 55, 18 ) .. "Elev N Per Slab Poly" = POLYGON V1 = ( 55, 18 ) V2 = ( 62, 18 ) V3 = ( 62, 20 ) V4 = ( 55, 20 ) .. "Atr Upper Fl Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 14 ) V4 = ( 0, 14 ) .. "El Lob Upper Poly" = POLYGON V1 = ( 48, -6 ) V2 = ( 62, -6 ) V3 = ( 62, 10 ) V4 = ( 55, 10 ) V5 = ( 55, 20 ) V6 = ( 48, 20 ) .. "S Lab Flr Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 48 ) V4 = ( 0, 48 ) .. "S Lab Int Slab Poly" = POLYGON V1 = ( 2, 2 ) V2 = ( 46, 2 ) V3 = ( 46, 48 ) V4 = ( 2, 48 ) .. "S Lab S Per Slab Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 46, 2 ) V4 = ( 2, 2 ) .. "S Lab W Per Slab Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 2, 2 ) V3 = ( 2, 48 ) V4 = ( 0, 48 ) .. "S Lab E Per Slab Poly" = POLYGON V1 = ( 48, 0 ) V2 = ( 48, 48 ) V3 = ( 46, 48 ) V4 = ( 46, 2 ) .. "N Lab Flr Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 48 ) V4 = ( 0, 48 ) .. "N Lab Int Slab Poly" = POLYGON V1 = ( 2, 0 ) V2 = ( 46, 0 ) V3 = ( 46, 46 ) V4 = ( 2, 46 ) .. "N Lab W Per Slab Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 2, 0 ) V3 = ( 2, 46 ) V4 = ( 0, 48 ) .. "N Lab N Per Slab Poly" = POLYGON V1 = ( 0, 48 ) V2 = ( 2, 46 ) V3 = ( 46, 46 ) V4 = ( 48, 48 ) .. "N Lab E Per Slab Poly" = POLYGON V1 = ( 46, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 48 ) V4 = ( 46, 46 ) .. "N Lab Flr Poly - SMirro" = POLYGON V1 = ( 0, 0 ) V2 = ( 48, 0 ) V3 = ( 48, 48 ) V4 = ( 0, 48 ) .. "Sky Box W End Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 7, 0 ) V3 = ( 7, 8.5 ) .. "Sky Box E End Poly" = POLYGON V1 = ( 0, 0 ) V2 = ( 7, 0 ) V3 = ( 0, 8.5 ) .. "Atr Main Flr Plan Poly - SMirro" = POLYGON V1 = ( 0, 0 ) V2 = ( 14, 0 ) V3 = ( 14, 48 ) V4 = ( 20, 48 ) V5 = ( 20, 55 ) V6 = ( 10, 55 ) V7 = ( 10, 62 ) V8 = ( -6, 62 ) V9 = ( -6, 48 ) V10 = ( 0, 48 ) .. "Elev Flr Plan Poly - SMirro" = POLYGON V1 = ( 10, 55 ) V2 = ( 20, 55 ) V3 = ( 20, 62 ) V4 = ( 10, 62 ) .. $ --------------------------------------------------------- $ Wall Parameters $ --------------------------------------------------------- $ --------------------------------------------------------- $ Fixed and Building Shades $ --------------------------------------------------------- "Conifer Treeline S of Bldg" = FIXED-SHADE X-REF = -130 Y-REF = -110 HEIGHT = 13 WIDTH = 200 AZIMUTH = 180 .. $ --------------------------------------------------------- $ Misc Cost Related Objects $ --------------------------------------------------------- "Baseline Data" = BASELINE FIRST-COST = 4.2e+006 LABOR-INFLTN = 5 MATERIALS-INFLTN = 10 .. $ ********************************************************* $ ** ** $ ** Floors / Spaces / Walls / Windows / Doors ** $ ** ** $ ********************************************************* "Off Bsmt Flr" = FLOOR X = 24 Z = -10 AZIMUTH = 180 POLYGON = "Off Floor Polygon" SHAPE = POLYGON FLOOR-HEIGHT = 10 SPACE-HEIGHT = 8 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Off Bsmt Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Bsmt Occup Sch" LIGHTING-SCHEDUL = ( "Bsmt Area Lighting Sch" ) TASK-LIGHT-SCH = "Bsmt Occup Sch" EQUIP-SCHEDULE = ( "Off Bldg Misc Sch" ) SOURCE-SCHEDULE = "IT Rm Heat Output Sch" SOURCE-TYPE = ELECTRIC SOURCE-POWER = 20000 INF-METHOD = NONE PEOPLE-HG-LAT = 198.918 PEOPLE-HG-SENS = 248.742 TASK-LIGHTING-KW = 0.04 EQUIP-LATENT = ( 0 ) EQUIP-SENSIBLE = ( 1 ) NUMBER-OF-PEOPLE = 1 LIGHTING-W/AREA = ( 1 ) EQUIPMENT-W/AREA = ( 0.75 ) FRAC-LEAK-AREA = 0 AREA/PERSON = 188.667 POLYGON = "Off Floor Polygon" LTG-SPEC-METHOD = POWER-DEFINITION C-SUB-SRC-BTUH = ( 0, 0, 0 ) C-SUB-SRC-KW = ( 0, 0, 0 ) C-ACTIVITY-DESC = *Office (Executive/Private) (34%)* .. "Off Bsmt Ceilg" = INTERIOR-WALL NEXT-TO = "Off Bsmt Pln Spc" CONSTRUCTION = "Ceilg Con" INT-WALL-TYPE = STANDARD LOCATION = TOP .. "Off Bsmt W Wall C" = INTERIOR-WALL NEXT-TO = "Atr Bsmt Sp" CONSTRUCTION = "Int Wall Con" Y = 18 HEIGHT = 10 WIDTH = 16 LOCATION = SPACE-V2 .. "Off Bsmt N Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V1 .. "Off Bsmt W Wall N" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" X = 48 WIDTH = 8 LOCATION = SPACE-V2 .. "Off Bsmt S Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V3 .. "Off Bsmt E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V4 .. "Off Bsmt W Wall S" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" X = 48 Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Off Bsmt Int Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" LOCATION = BOTTOM POLYGON = "Off Bsmt Int Slab Poly - Mirro" .. "Off Bsmt E Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" AZIMUTH = 90 TILT = 180 LOCATION = BOTTOM POLYGON = "Off Bsmt E Per Slab Poly - Mirro" .. "Off Bsmt N Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" AZIMUTH = 90 TILT = 180 LOCATION = BOTTOM POLYGON = "Off Bsmt N Per Slab Poly - Mirro" .. "Off Bsmt S Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" AZIMUTH = 90 TILT = 180 LOCATION = BOTTOM POLYGON = "Off Bsmt S Per Slab Poly - Mirro" .. "Off Bsmt W Per Slab S" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" LOCATION = BOTTOM POLYGON = "Off Bsmt W Per Slab S Poly - Mir" .. "Off Bsmt W Per Slab N" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" LOCATION = BOTTOM POLYGON = "Off Bsmt W Per Slab N Poly - Mir" .. "Off Bsmt W Int Slab C" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" LOCATION = BOTTOM POLYGON = "Off Bsmt W Int Slab C Poly - Mir" .. "Off Bsmt Pln Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "Off Floor Polygon" .. "Off Bsmt Pln N Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V1 .. "Off Bsmt Pln W Wall N" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" WIDTH = 8 LOCATION = SPACE-V2 .. "Off Bsmt Pln S Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V3 .. "Off Bsmt Pln E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V4 .. "Off Bsmt Pln W Wall S" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Off Grd Flr" = FLOOR X = 24 AZIMUTH = 180 POLYGON = "Off Floor Polygon" SHAPE = POLYGON FLOOR-HEIGHT = 10 SPACE-HEIGHT = 8 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Off Grd Flr Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Grd Fl Occup Sch" LIGHTING-SCHEDUL = ( "Office Area Lighting Sch" ) TASK-LIGHT-SCH = "Grd Fl Occup Sch" EQUIP-SCHEDULE = ( "Off Bldg Misc Sch" ) LIGHTING-TYPE = ( REC-FLUOR-NV ) INF-METHOD = S-G INF-FLOW/AREA = 0 NEUTRAL-ZONE-HT = 5 PEOPLE-HG-LAT = 473.961 PEOPLE-HG-SENS = 274.885 TASK-LIGHTING-KW = 0.2 EQUIP-LATENT = ( 0 ) EQUIP-SENSIBLE = ( 1 ) NUMBER-OF-PEOPLE = 5 LIGHTING-W/AREA = ( 1 ) EQUIPMENT-W/AREA = ( 0.75 ) DAYLIGHTING = YES LIGHT-REF-POINT1 = ( 20, 20 ) MIN-POWER-FRAC = {parameter("DayLgtPwrFrac")} MIN-LIGHT-FRAC = {parameter("DayLgtLgtFrac")} DAYLIGHT-REP-SCH = "Hourly Report Schedule" HOR-LEAK-FRAC = 0.3 FRAC-LEAK-AREA = 0 AREA/PERSON = 307.85 POLYGON = "Off Floor Polygon" C-SUB-SRC-BTUH = ( 0, 0, 0 ) C-SUB-SRC-KW = ( 0, 0, 0 ) C-ACTIVITY-DESC = *Comm/Ind Work (Gen, Low)* .. "Off GF N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V1 .. "Off GF N Win #1" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 5.79956 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off GF N Win #2" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 28.0359 Y = 2 HEIGHT = 4.66667 WIDTH = 5.81067 FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off GF W Wall S" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Off GF S Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "Off GF S Win E" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 29 Y = 2 HEIGHT = 5.5 WIDTH = 15 OVERHANG-A = 2.5 OVERHANG-B = 1 OVERHANG-W = 20 OVERHANG-D = {parameter("S Off Win GF OH Length")} FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off GF S Win W" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" X = 1 Y = 2 HEIGHT = 5.5 WIDTH = 17.5 OVERHANG-A = 2.5 OVERHANG-B = 1 OVERHANG-W = 22.5 OVERHANG-D = {parameter("S Off Win GF OH Length")} .. "Off S Doors" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 6.2 X = 21 HEIGHT = 6.5 WIDTH = 6 .. "Off GF E Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V4 .. "Off GF E Win #1" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 1.58986 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off GF E Win #2" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 7.05292 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off GF E Win #3" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 12.516 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off GF E Win #4" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 23.4421 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off GF E Win #5" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 31.4643 Y = 2 HEIGHT = 4.66667 WIDTH = 6.38667 FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off E Doors" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 6.2 X = 16 HEIGHT = 6.5 WIDTH = 6 .. "Off GF W Wall N" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" WIDTH = 8 LOCATION = SPACE-V2 .. "Off GF Flr" = INTERIOR-WALL NEXT-TO = "Off Bsmt Pln Spc" CONSTRUCTION = "Int Hydron Flr Con" LOCATION = BOTTOM .. "Off GF Ceilg" = INTERIOR-WALL NEXT-TO = "Off GF Pln Spc" CONSTRUCTION = "Ceilg Con" LOCATION = TOP .. "Off GF W Wall C" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD Y = 18 HEIGHT = 10 WIDTH = 16 LOCATION = SPACE-V2 .. "Off GF Pln Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "Off Floor Polygon" .. "Off GF Pln N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V1 .. "Off GF Pln W Wall N" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" WIDTH = 8 LOCATION = SPACE-V2 .. "Off GF Pln S Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "Off GF Pln E Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V4 .. "Off GF Pln W Wall S" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Off Top Flr" = FLOOR X = 24 Z = 10 AZIMUTH = 180 POLYGON = "Off Floor Polygon" SHAPE = POLYGON FLOOR-HEIGHT = 10 SPACE-HEIGHT = 8 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Off Top Flr Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Top Fl Occup Sch" LIGHTING-SCHEDUL = ( "Office Area Lighting Sch" ) TASK-LIGHT-SCH = "Top Fl Occup Sch" EQUIP-SCHEDULE = ( "Off Bldg Misc Sch" ) LIGHTING-TYPE = ( REC-FLUOR-NV ) INF-METHOD = S-G INF-FLOW/AREA = 0 PEOPLE-HG-LAT = 198.918 PEOPLE-HG-SENS = 248.742 TASK-LIGHTING-KW = 0.2 EQUIP-LATENT = ( 0 ) EQUIP-SENSIBLE = ( 1 ) NUMBER-OF-PEOPLE = 6 LIGHTING-W/AREA = ( 1 ) EQUIPMENT-W/AREA = ( 0.75 ) DAYLIGHTING = YES LIGHT-REF-POINT1 = ( 20, 20 ) MIN-POWER-FRAC = {parameter("DayLgtPwrFrac")} MIN-LIGHT-FRAC = {parameter("DayLgtLgtFrac")} FRAC-LEAK-AREA = 0 AREA/PERSON = 188.667 POLYGON = "Off Floor Polygon" C-SUB-SRC-BTUH = ( 0, 0, 0 ) C-SUB-SRC-KW = ( 0, 0, 0 ) C-ACTIVITY-DESC = *Office (Executive/Private) (34%)* .. "Off TF N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V1 .. "Off TF N Win #1" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 5.79956 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF N Win #2" = WINDOW GLASS-TYPE = "Northerm 3255 Casement Win" FRAME-WIDTH = 0.166667 X = 28.0359 Y = 2 HEIGHT = 4.66667 WIDTH = 5.81067 FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off TF W Wall N" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" WIDTH = 8 LOCATION = SPACE-V2 .. "Off TF S Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "Off TF S Win E" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 27 Y = 2 HEIGHT = 5.5 WIDTH = 16.25 OVERHANG-A = 2.5 OVERHANG-B = 1 OVERHANG-W = 21.5 OVERHANG-D = {parameter("S Off Win TF OH Length")} FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off TF S Win W" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 1 Y = 2 HEIGHT = 5.5 WIDTH = 16.25 OVERHANG-A = 2.5 OVERHANG-B = 1 OVERHANG-W = 21.5 OVERHANG-D = {parameter("S Off Win TF OH Length")} FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off TF E Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V4 .. "Off TF E Win #1" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 1.58986 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF E Win #2" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 7.05292 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF E Win #3" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 12.516 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF E Win #4" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 17.979 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF E Win #5" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 23.4421 Y = 2.10833 HEIGHT = 4.78333 WIDTH = 2.28333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Off TF E Win #6" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.166667 X = 31.4643 Y = 2 HEIGHT = 4.66667 WIDTH = 6.38667 FRAME-CONDUCT = 0.567 SPACER-TYPE = ALUMINUM .. "Off TF W Wall S" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Off TF Flr" = INTERIOR-WALL NEXT-TO = "Off GF Pln Spc" CONSTRUCTION = "Int Hydron Flr Con" LOCATION = BOTTOM .. "Off TF Ceilg" = INTERIOR-WALL NEXT-TO = "Off TF Pln Spc" CONSTRUCTION = "Ceilg Con" LOCATION = TOP .. "Off TF W Wall C" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" Y = 18 HEIGHT = 10 WIDTH = 16 LOCATION = SPACE-V2 .. "Off TF Pln Spc" = SPACE SHAPE = POLYGON ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "Off Roof Polygon 1 Wall 1" .. "Off TF Pln N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V1 .. "Off TF Pln W Wall N" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" WIDTH = 8 LOCATION = SPACE-V2 .. "Off TF Pln S Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "Off TF Pln E Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V4 .. "Flat Roof" = EXTERIOR-WALL CONSTRUCTION = "Blown-In Roof Con" LOCATION = TOP .. "Off TF Pln W Wall S" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Y = 34 WIDTH = 8 LOCATION = SPACE-V2 .. "Atr Bsmt Flr" = FLOOR X = -86 Y = -28 Z = -10 AZIMUTH = 360 POLYGON = "Atr Main Flr Plan Poly" SHAPE = POLYGON FLOOR-HEIGHT = 10 SPACE-HEIGHT = 8 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Atr Bsmt Sp" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Atr Bsmt Occ Sch" LIGHTING-SCHEDUL = ( "Bsmt Area Lighting Sch" ) EQUIP-SCHEDULE = ( "Atr Bsmt Eq Sch" ) PEOPLE-HG-LAT = 250 PEOPLE-HG-SENS = 250 NUMBER-OF-PEOPLE = 1 LIGHTING-W/AREA = ( 1.14667 ) TASK-LT-W/AREA = 0 EQUIPMENT-W/AREA = ( 0.75 ) AREA/PERSON = 49.7788 POLYGON = "Atr Main Flr Plan Poly" C-ACTIVITY-DESC = *Utility Corredor Basement* .. "At Bsmt Ceil" = INTERIOR-WALL NEXT-TO = "At Bsmt Plnm" CONSTRUCTION = "Ceilg Con" LOCATION = TOP .. "At Bsmt Int Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" Y = 0 AZIMUTH = 180 TILT = 0 LOCATION = BOTTOM POLYGON = "Atr Interior Slab Poly" .. "At S Bsmt E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V3 .. "At N Bsmt E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V7 .. "At W Bsmt N Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V8 .. "At N Bsmt W Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V9 .. "At W Bsmt C Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V10 .. "At S Bsmt W Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" X = 0 Y = 0 Z = 0 HEIGHT = 8 AZIMUTH = -180 LOCATION = SPACE-V1 .. "At W Bsmt S Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V2 .. "Atr Bsmt W Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 2 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "Atr Bsmt W Per Slab Poly" .. "Atr Bsmt S Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 110 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "Atr Bsmt S Per Slab Poly" .. "Atr Bsmt N Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 103 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "Atr Bsmt N Per Slab Poly" .. "At Bsmt Plnm" = SPACE SHAPE = POLYGON ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "Atr Main Flr Plan Poly" C-ACTIVITY-DESC = *Atrium Bsmt Plenum* .. "At S Bsmt Pl E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V3 .. "At N Bsmt Pl E Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" Z = 0 LOCATION = SPACE-V7 .. "At W Bsmt Pl N Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V8 .. "At N Bsmt Pl W Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V9 .. "At W Bsmt Pl W Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" LOCATION = SPACE-V10 .. "At S Bsmt Pl W Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" X = 0 Y = 0 Z = 0 HEIGHT = 2 AZIMUTH = -180 LOCATION = SPACE-V1 .. "At W Bsmt Pl S Wall" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" X = 48 Y = 0 Z = 0 HEIGHT = 2 WIDTH = 6 AZIMUTH = -90 LOCATION = SPACE-V2 .. "Elev Shaft Flr" = FLOOR X = -86 Y = -28 Z = -10 AZIMUTH = 360 POLYGON = "Elev Flr Plan Poly" SHAPE = POLYGON FLOOR-HEIGHT = 46 SPACE-HEIGHT = 46 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Elev Shaft Sp" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Elev Occ Sch" LIGHTING-SCHEDUL = ( "Elev Occ Sch" ) EQUIP-SCHEDULE = ( "Off Bldg OffEq Sch" ) INF-METHOD = NONE INF-FLOW/AREA = 0 PEOPLE-HG-LAT = 250 PEOPLE-HG-SENS = 250 LIGHTING-KW = ( 0.01 ) TASK-LIGHTING-KW = 0.01 EQUIPMENT-KW = ( 0 ) LIGHTING-W/AREA = ( 0 ) TASK-LT-W/AREA = 0.01 EQUIPMENT-W/AREA = ( 0.75 ) LIGHT-REF-POINT1 = ( 24.48, 13, 2.5 ) ZONE-FRACTION1 = 0.619068 LIGHT-SET-POINT1 = 50 LIGHT-CTRL-TYPE1 = CONTINUOUS MAX-GLARE = 20 AREA/PERSON = 49.7788 POLYGON = "Elev Flr Plan Poly" C-ACTIVITY-DESC = *Elevator Shaft* .. "El Sh E Wall U" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" X = 62 Y = 10 Z = 30 HEIGHT = 16 WIDTH = 10 AZIMUTH = -270 TILT = 90 LOCATION = SPACE-V2 SHADING-SURFACE = YES .. "El Sh N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Z = 10 HEIGHT = 36 LOCATION = SPACE-V3 .. "El Sh W Wall 4" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Z = 40 HEIGHT = 6 LOCATION = SPACE-V4 .. "El Sh S Wall 4" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Z = 40 HEIGHT = 6 LOCATION = SPACE-V1 .. "Elev Shaft Roof" = EXTERIOR-WALL CONSTRUCTION = "Blown-In Roof Con" LOCATION = TOP .. "El Sh W Wall 1" = INTERIOR-WALL NEXT-TO = "Atr Bsmt Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD HEIGHT = 10 LOCATION = SPACE-V4 .. "El Sh W Wall 2" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD Z = 10 HEIGHT = 10 LOCATION = SPACE-V4 .. "El Sh W Wall 3" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD Z = 20 HEIGHT = 20 LOCATION = SPACE-V4 .. "El Sh S Wall 1" = INTERIOR-WALL NEXT-TO = "Atr Bsmt Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD HEIGHT = 10 LOCATION = SPACE-V1 .. "El Sh S Wall 2" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD Z = 10 HEIGHT = 10 LOCATION = SPACE-V1 .. "El Sh S Wall 3" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" INT-WALL-TYPE = STANDARD Z = 20 HEIGHT = 20 LOCATION = SPACE-V1 .. "El Sh E Wall Bsmt" = INTERIOR-WALL NEXT-TO = "Off Bsmt Spc" CONSTRUCTION = "Int Wall Con" X = 62 HEIGHT = 10 LOCATION = SPACE-V2 .. "El Sh E Wall Grd Fl" = INTERIOR-WALL NEXT-TO = "Off Grd Flr Spc" CONSTRUCTION = "Int Wall Con" Z = 10 HEIGHT = 10 LOCATION = SPACE-V2 .. "El Sh E Wall Top Fl" = INTERIOR-WALL NEXT-TO = "Off Top Flr Spc" CONSTRUCTION = "Int Wall Con" Z = 20 HEIGHT = 10 LOCATION = SPACE-V2 .. "El Sh Int Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" X = 117 Y = 0 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "Elev Int Slab Poly" .. "El Sh N Wall Bsmt" = UNDERGROUND-WALL CONSTRUCTION = "Bsmt Wall Con" HEIGHT = 10 LOCATION = SPACE-V3 .. "El Sh N Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 117 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "Elev N Per Slab Poly" .. "Atr Ground Flr" = FLOOR X = -86 Y = -28 AZIMUTH = 360 POLYGON = "Atr Main Flr Plan Poly" SHAPE = POLYGON FLOOR-HEIGHT = 10 SPACE-HEIGHT = 8 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "At Grd Fl Sp" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "At GF Occ Sch" LIGHTING-SCHEDUL = ( "Atr Grd Fl Occ Sch" ) EQUIP-SCHEDULE = ( "Off Bldg OffEq Sch" ) INF-METHOD = S-G INF-FLOW/AREA = 0 NEUTRAL-ZONE-HT = 0 PEOPLE-HG-LAT = 250 PEOPLE-HG-SENS = 250 NUMBER-OF-PEOPLE = 1 LIGHTING-W/AREA = ( 0.7 ) TASK-LT-W/AREA = 0 EQUIPMENT-W/AREA = ( 0.75 ) LIGHT-REF-POINT1 = ( 36.97, 13, 2.5 ) ZONE-FRACTION1 = 0.619068 LIGHT-SET-POINT1 = 50 LIGHT-CTRL-TYPE1 = CONTINUOUS MAX-GLARE = 20 FRAC-LEAK-AREA = 0 AREA/PERSON = 450 POLYGON = "Atr Main Flr Plan Poly" C-ACTIVITY-DESC = *Hallway* .. "Atr Grd Fl S Wall E" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "At Grd Fl S El Lob Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 1 Y = 3 HEIGHT = 4 WIDTH = 2.5 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "S Lobby Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 6 HEIGHT = 7 WIDTH = 3 .. "At Grd Fl N Wall E" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V7 .. "N Lobby Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 1.5 HEIGHT = 7 WIDTH = 3 .. "At Grd Fl W Wall C" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V10 .. "West End Door 1" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 4 HEIGHT = 7 WIDTH = 3 .. "West End Door 2" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 7 HEIGHT = 7 WIDTH = 3 .. "At Grd Fl" = INTERIOR-WALL NEXT-TO = "At Bsmt Plnm" CONSTRUCTION = "Int Hydron Flr Con" Y = 14 AZIMUTH = 180 LOCATION = BOTTOM POLYGON = "Atr Main Flr Plan Poly - Mirro" .. "At Grd Fl Ceil" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Ceilg Con" X = 0 Y = 0 Z = 8 AZIMUTH = 180 TILT = 0 LOCATION = TOP .. "At Grd Fl Pln Sp" = SPACE SHAPE = POLYGON ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "Atr Main Flr Plan Poly" C-ACTIVITY-DESC = *Plenum above Atrium Grd Flr Spc* .. "At Grd Flr S Pln Wall E" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V3 .. "At Grd Fl N Pln Wall E" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V7 .. "At Grd Fl W Pln Wall C" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V10 .. "Atrium Flr" = FLOOR X = -86 Y = -28 Z = 10 AZIMUTH = 360 POLYGON = "Atr Main Flr Plan Poly" SHAPE = POLYGON FLOOR-HEIGHT = 20 SPACE-HEIGHT = 20 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "Atrium Sp" = SPACE SHAPE = POLYGON ZONE-TYPE = CONDITIONED PEOPLE-SCHEDULE = "Atrium Occupancy Sch" LIGHTING-SCHEDUL = ( "Office Area Lighting Sch" ) EQUIP-SCHEDULE = ( "Off Bldg OffEq Sch" ) INF-METHOD = S-G INF-FLOW/AREA = 0 NEUTRAL-ZONE-HT = 0 PEOPLE-HG-LAT = 250 PEOPLE-HG-SENS = 250 NUMBER-OF-PEOPLE = 2 LIGHTING-W/AREA = ( 1 ) TASK-LT-W/AREA = 0 EQUIPMENT-W/AREA = ( 0.75 ) DAYLIGHTING = YES LIGHT-REF-POINT1 = ( 24.48, 13, 2.5 ) ZONE-FRACTION1 = 0.619068 LIGHT-SET-POINT1 = 50 LIGHT-CTRL-TYPE1 = CONTINUOUS MAX-GLARE = 20 MIN-POWER-FRAC = {parameter("DayLgtPwrFrac")} MIN-LIGHT-FRAC = {parameter("DayLgtLgtFrac")} DAYLIGHT-REP-SCH = "Hourly Report Schedule" FRAC-LEAK-AREA = 0 AREA/PERSON = 49.7788 POLYGON = "Atr Main Flr Plan Poly" C-ACTIVITY-DESC = *Atrium & Classrooms* .. "El Lob At Lev S Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" HEIGHT = 20 LOCATION = SPACE-V3 .. "El Lob At Lev S Win E" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 3 Y = 3 HEIGHT = 4 WIDTH = 7.5 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "El Lob At lev S Win W" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT FRAME-WIDTH = 0.108333 X = 2 Y = 13 HEIGHT = 4 WIDTH = 7.5 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "El Lob At Lev N Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" LOCATION = SPACE-V7 .. "El Lob At Lev N Win L" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 1.5 Y = 3 HEIGHT = 4 WIDTH = 3 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "El Lob At Lev N Win U" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT FRAME-WIDTH = 0.108333 X = 1.5 Y = 15 HEIGHT = 4 WIDTH = 3 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "Atr W Wall C" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" HEIGHT = 18 LOCATION = SPACE-V10 .. "W Wall Lower Atrium Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT X = 3 Y = 3 HEIGHT = 4 WIDTH = 7.5 SPACER-TYPE = INSULATED .. "W Wall Upper Atrium Window" = WINDOW LIKE = "El Lob At lev S Win W" GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT Y = 13.5 HEIGHT = 3 .. "El Lob W N Roof Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Z = 12 HEIGHT = 8 LOCATION = SPACE-V8 SHADING-SURFACE = YES .. "N Lab Roof Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 1.5 Y = 0 HEIGHT = 7 WIDTH = 3 .. "Atr S Roof Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" X = 0 Y = 0 Z = 12 HEIGHT = 6 TILT = 90 LOCATION = SPACE-V1 .. "Atr S Roof Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT FRAME-WIDTH = 0.108333 X = 4 Y = 1 HEIGHT = 4 WIDTH = 40 FRAME-CONDUCT = 0.434 SPACER-TYPE = INSULATED .. "El Lob W Roof Wall S" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" X = 48 Y = 0 Z = 12 HEIGHT = 8 WIDTH = 6 TILT = 90 LOCATION = SPACE-V2 SHADING-SURFACE = YES .. "S Lab Roof Door" = DOOR LIKE = "West End Door 2" CONSTRUCTION = "Opaque Door Con" X = 1.5 .. "Atr N Roof Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" X = 48 Y = 14 Z = 12 HEIGHT = 6 TILT = 90 LOCATION = SPACE-V9 .. "El Lob W Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Z = 18 HEIGHT = 2 WIDTH = 14 AZIMUTH = -90 LOCATION = SPACE-V9 .. "Atrium Roof" = EXTERIOR-WALL CONSTRUCTION = "Blown-In Roof Con" Z = 18 LOCATION = TOP POLYGON = "Atr Upper Fl Poly" .. "El Lobby Roof" = EXTERIOR-WALL CONSTRUCTION = "Blown-In Roof Con" LOCATION = TOP POLYGON = "El Lob Upper Poly" .. "El Lob Atr Lev E U Wall" = EXTERIOR-WALL CONSTRUCTION = "Off Wall Con" Y = -6 Z = 10 HEIGHT = 10 WIDTH = 16 LOCATION = SPACE-V4 .. "Atrium Fl" = INTERIOR-WALL NEXT-TO = "At Grd Fl Pln Sp" CONSTRUCTION = "Int Hydron Flr Con" Y = 14 AZIMUTH = 180 TILT = 180 LOCATION = BOTTOM POLYGON = "Atr Main Flr Plan Poly - Mirro" .. "S Lab Flr" = FLOOR X = -86 Y = -76 AZIMUTH = 360 POLYGON = "S Lab Flr Poly" SHAPE = POLYGON FLOOR-HEIGHT = 22 SPACE-HEIGHT = 20 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "S Lab Spc" = SPACE SHAPE = POLYGON FURN-FRACTION = 0.3 ZONE-TYPE = CONDITIONED TEMPERATURE = ( 73 ) PEOPLE-SCHEDULE = "S Lab Occ" LIGHTING-SCHEDUL = ( "Office Area Lighting Sch" ) TASK-LIGHT-SCH = "S Lab Ltg" EQUIP-SCHEDULE = ( "S Lab Eq Sch" ) INF-SCHEDULE = "S Lab Inf Sch" INF-METHOD = S-G INF-FLOW/AREA = 0 NEUTRAL-ZONE-HT = 0 PEOPLE-HG-LAT = 427.396 PEOPLE-HG-SENS = 270.087 EQUIPMENT-KW = ( 0 ) NUMBER-OF-PEOPLE = 2 LIGHTING-W/AREA = ( 1 ) TASK-LT-W/AREA = 0.02 EQUIPMENT-W/AREA = ( 0.75 ) FURN-WEIGHT = 200 DAYLIGHTING = YES LIGHT-REF-POINT1 = ( 24, 24, 0 ) ZONE-FRACTION1 = 0.695833 LIGHT-SET-POINT1 = 50 LIGHT-CTRL-TYPE1 = CONTINUOUS VIEW-AZIMUTH = 180 MAX-GLARE = 22 MIN-POWER-FRAC = {parameter("DayLgtPwrFrac")} MIN-LIGHT-FRAC = {parameter("DayLgtLgtFrac")} DAYLIGHT-REP-SCH = "Hourly Report Schedule" FRAC-LEAK-AREA = 0 AREA/PERSON = 1150 POLYGON = "S Lab Flr Poly" C-ACTIVITY-DESC = *Comm/Ind Work (Gen, High) (95%)* .. "S Wall S Lab" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V1 .. "Low S Win C" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 19.5 Y = 2 HEIGHT = 5 WIDTH = 7.5 OVERHANG-A = 0 OVERHANG-B = 0 OVERHANG-W = 0 OVERHANG-D = 0 FRAME-CONDUCT = 0.53 SPACER-TYPE = INSULATED .. "Mid S Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 12 Y = 7.5 HEIGHT = 5 WIDTH = 22.5 OVERHANG-A = 0 OVERHANG-B = 0 OVERHANG-W = 0 OVERHANG-D = 0 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Top S Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT FRAME-WIDTH = 0.108333 X = 12 Y = 13 HEIGHT = 5 WIDTH = 22.5 OVERHANG-A = 0 OVERHANG-B = 0 OVERHANG-W = 0 OVERHANG-D = 0 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "Low S Win E" = WINDOW GLASS-TYPE = "Northerm 3255 Casement Win" X = 27.5 Y = 2 HEIGHT = 5 WIDTH = 7.5 SPACER-TYPE = INSULATED .. "Low S Win W" = WINDOW GLASS-TYPE = "Northerm 3255 Casement Win" X = 11.5 Y = 2 HEIGHT = 5 WIDTH = 7.5 SPACER-TYPE = INSULATED .. "E Wall S Lab" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V2 .. "S Lab E Clsrm Win" = WINDOW GLASS-TYPE = "Northerm 3255 Casement Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT X = 34 Y = 13 HEIGHT = 5 WIDTH = 5 .. "S Lab E Big Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 15 X = 6 HEIGHT = 14 WIDTH = 12 .. "S Lab E Man Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 34 HEIGHT = 7 WIDTH = 3 .. "W Wall S Lab" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V4 .. "S Lab Low W Win" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT X = 2 Y = 2 HEIGHT = 4.5 WIDTH = 5 .. "S Lab W Clsrm Win" = WINDOW GLASS-TYPE = "Northerm 3255 Casement Win" WIN-SPEC-METHOD = GLASS-TYPE-INPUT X = 9 Y = 13 HEIGHT = 5 WIDTH = 5 .. "S Lab W Big Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 15 X = 30 HEIGHT = 14 WIDTH = 12 .. "S Lab W Man Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 9 HEIGHT = 7 WIDTH = 3 .. "S Lab Ceiling" = INTERIOR-WALL NEXT-TO = "S Lab Pln Spc" CONSTRUCTION = "Ceilg Con" LOCATION = TOP .. "S Lab N Wall GF" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" X = 48 Y = 48 HEIGHT = 10 AZIMUTH = 0 LOCATION = SPACE-V1 .. "S Lab N Wall TF" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" X = 48 Y = 48 Z = 10 HEIGHT = 12 AZIMUTH = 0 LOCATION = SPACE-V1 .. "S Lab E Wall N L" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" Y = 42 HEIGHT = 10 WIDTH = 6 LOCATION = SPACE-V2 .. "S Lab E Wall N U" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" Y = 42 Z = 10 HEIGHT = 12 WIDTH = 6 LOCATION = SPACE-V2 .. "S Lab Interior Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" X = 48 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "S Lab Int Slab Poly" .. "S Lab S Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 48 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "S Lab S Per Slab Poly" .. "S Lab E Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 0 AZIMUTH = 180 TILT = 0 LOCATION = BOTTOM POLYGON = "S Lab E Per Slab Poly" .. "S Lab W Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" AZIMUTH = 180 TILT = 0 LOCATION = BOTTOM POLYGON = "S Lab W Per Slab Poly" .. "S Lab Pln Spc" = SPACE SHAPE = POLYGON FURNITURE-TYPE = LIGHT ZONE-TYPE = PLENUM INF-METHOD = NONE INF-FLOW/AREA = 0 POLYGON = "S Lab Flr Poly" LOCATION = PLENUM-SPACE C-ACTIVITY-DESC = *S Lab Plenum* .. "S Wall S Lab Plnm" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V1 .. "E Wall S Lab Plnm" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V2 .. "W Wall S Lab Plnm" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V4 .. "S Lab Green Roof" = EXTERIOR-WALL CONSTRUCTION = "Green Lab Roof Con" LOCATION = TOP .. "N Lab Flr" = FLOOR X = -86 Y = -14 AZIMUTH = 360 POLYGON = "N Lab Flr Poly" SHAPE = POLYGON FLOOR-HEIGHT = 22 SPACE-HEIGHT = 22 C-DIAGRAM-DATA = *Shell 1 Diag Data* .. "N Lab Spc" = SPACE X = 0 Y = 0 SHAPE = POLYGON ZONE-TYPE = CONDITIONED TEMPERATURE = ( 73 ) PEOPLE-SCHEDULE = "N Lab Occ Sch" LIGHTING-SCHEDUL = ( "N Lab Lgt Sch" ) EQUIP-SCHEDULE = ( "N Lab Eq Sch" ) INF-SCHEDULE = "N Lab Inf Sch" INF-METHOD = S-G INF-FLOW/AREA = 0 NEUTRAL-ZONE-HT = 0 PEOPLE-HG-LAT = 367.565 PEOPLE-HG-SENS = 265.009 EQUIPMENT-KW = ( 0 ) EQUIP-LATENT = ( 0 ) EQUIP-SENSIBLE = ( 1 ) NUMBER-OF-PEOPLE = 2 LIGHTING-W/AREA = ( 1 ) EQUIPMENT-W/AREA = ( 0.75 ) DAYLIGHTING = YES LIGHT-REF-POINT1 = ( 20, 20 ) MIN-POWER-FRAC = {parameter("DayLgtPwrFrac")} MIN-LIGHT-FRAC = {parameter("DayLgtLgtFrac")} DAYLIGHT-REP-SCH = "Hourly Report Schedule" FRAC-LEAK-AREA = 0 AREA/PERSON = 1200 POLYGON = "N Lab Flr Poly" C-SUB-SRC-BTUH = ( 0, 0, 0 ) C-SUB-SRC-KW = ( 0, 0, 0 ) C-ACTIVITY-DESC = *Comm/Ind Work* .. "N Lab Sky Wall" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" X = 10 Y = 41 Z = 22 HEIGHT = 8.5 WIDTH = 28 LOCATION = SPACE-V1 .. "Skylight" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" X = 2.5 Y = 2 HEIGHT = 4 WIDTH = 22.5 .. "N Lab E Wall" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V2 .. "N Lab E Win S" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 6.29833 Y = 3.10833 HEIGHT = 4.78333 WIDTH = 8.90333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "N Lab E Win N" = WINDOW GLASS-TYPE = "Northerm 3255 Fixed Win" FRAME-WIDTH = 0.108333 X = 32.7983 Y = 3.10833 HEIGHT = 4.78333 WIDTH = 8.90333 FRAME-CONDUCT = 0.482 SPACER-TYPE = INSULATED .. "N Lab E Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 22.5 HEIGHT = 7 WIDTH = 3 .. "N Lab N Wall" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V3 .. "N Lab N Big Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 15 X = 19 HEIGHT = 14 WIDTH = 10 .. "N Lab W Wall" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" LOCATION = SPACE-V4 .. "N Lab W Door" = DOOR CONSTRUCTION = "Opaque Door Con" INF-COEF = 3.1 X = 22.5 HEIGHT = 7 WIDTH = 3 .. "N Lab Green Roof" = EXTERIOR-WALL CONSTRUCTION = "Green Lab Roof Con" Z = 22 HEIGHT = 41 TILT = 0 LOCATION = SPACE-V1 .. "Sky Makeup Roof W" = EXTERIOR-WALL CONSTRUCTION = "Green Lab Roof Con" Y = 41 Z = 22 HEIGHT = 7 WIDTH = 10 TILT = 0 LOCATION = SPACE-V1 .. "Sky Makeup Roof E" = EXTERIOR-WALL CONSTRUCTION = "Green Lab Roof Con" X = 38 Y = 41 Z = 22 HEIGHT = 7 WIDTH = 10 TILT = 0 LOCATION = SPACE-V1 .. "Skylight Reflector" = EXTERIOR-WALL CONSTRUCTION = "Blown-In Roof Con" X = 38 Y = 48 Z = 22 HEIGHT = 11.01 WIDTH = 28 AZIMUTH = 0 TILT = 50.53 LOCATION = SPACE-V1 .. "Sky Box W End" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" X = 10 Y = 48 Z = 22 AZIMUTH = -90 LOCATION = SPACE-V1 POLYGON = "Sky Box W End Poly" .. "Sky Box E End Wall" = EXTERIOR-WALL CONSTRUCTION = "Lab Wall Con" X = 38 Y = 41 Z = 22 AZIMUTH = 90 LOCATION = SPACE-V1 POLYGON = "Sky Box E End Poly" .. "N Lab E Wall S L" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" HEIGHT = 10 WIDTH = 6 LOCATION = SPACE-V2 .. "N Lab E Wall S U" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" Z = 10 HEIGHT = 12 WIDTH = 6 LOCATION = SPACE-V2 .. "N Lab S Wall GF" = INTERIOR-WALL NEXT-TO = "At Grd Fl Sp" CONSTRUCTION = "Int Wall Con" HEIGHT = 10 LOCATION = SPACE-V1 .. "N Lab S Wall Atr" = INTERIOR-WALL NEXT-TO = "Atrium Sp" CONSTRUCTION = "Int Wall Con" Z = 10 HEIGHT = 12 LOCATION = SPACE-V1 .. "N Lab Int Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Interior Con" X = 48 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "N Lab Int Slab Poly" .. "N Lab W Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" AZIMUTH = 180 TILT = 0 LOCATION = BOTTOM POLYGON = "N Lab W Per Slab Poly" .. "N Lab N Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" X = 48 AZIMUTH = 0 LOCATION = BOTTOM POLYGON = "N Lab N Per Slab Poly" .. "N Lab E Per Slab" = UNDERGROUND-WALL CONSTRUCTION = "Slab Perimeter Con" LOCATION = BOTTOM .. $ ********************************************************* $ ** ** $ ** Performance Curves ** $ ** ** $ ********************************************************* $ ********************************************************* $ ** ** $ ** Electric & Fuel Meters ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Electric Meters $ --------------------------------------------------------- "EM1" = ELEC-METER TYPE = UTILITY SOURCE-SITE-EFF = 1 BLDG/SUB-METERS = ( "OBM", "ABM", "ESM", "OGM", "AGM", "NLM", "OTM", "ATM", "SLM" ) .. "OBM" = ELEC-METER TYPE = BUILDING .. "ABM" = ELEC-METER TYPE = BUILDING .. "ESM" = ELEC-METER TYPE = BUILDING .. "OGM" = ELEC-METER TYPE = BUILDING .. "AGM" = ELEC-METER TYPE = BUILDING .. "NLM" = ELEC-METER TYPE = BUILDING .. "OTM" = ELEC-METER TYPE = BUILDING .. "ATM" = ELEC-METER TYPE = BUILDING .. "SLM" = ELEC-METER TYPE = BUILDING .. $ --------------------------------------------------------- $ Fuel Meters $ --------------------------------------------------------- "FM1" = FUEL-METER TYPE = FUEL-OIL .. "BFOM Bsmt Oil Meter" = FUEL-METER TYPE = FUEL-OIL .. "GFOM Grd Fl Oil Meter" = FUEL-METER TYPE = FUEL-OIL .. "TFOM Top Fl Oil Meter" = FUEL-METER TYPE = FUEL-OIL .. $ --------------------------------------------------------- $ Master Meters $ --------------------------------------------------------- "MASTER-METERS 1" = MASTER-METERS MSTR-ELEC-METER = "EM1" MSTR-FUEL-METER = "FM1" .. $ ********************************************************* $ ** ** $ ** HVAC Circulation Loops / Plant Equipment ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Pumps $ --------------------------------------------------------- "Grd Fl HW Lp Pump" = PUMP FLOW-RATIO = 1.15 NUMBER = 1 HEAD = 50 HEAD-SETPT = 45 MOTOR-CLASS = HI-EFF CAP-CTRL = VAR-SPEED-PUMP ELEC-METER = "OGM" .. "Bsmt HW Pump" = PUMP FLOW-RATIO = 1.15 MOTOR-CLASS = HI-EFF CAP-CTRL = VAR-SPEED-PUMP .. "Top Fl HW Lp Pump" = PUMP FLOW-RATIO = 1.15 MOTOR-CLASS = HI-EFF CAP-CTRL = VAR-SPEED-PUMP .. $ --------------------------------------------------------- $ Heat Exchangers $ --------------------------------------------------------- $ --------------------------------------------------------- $ Circulation Loops $ --------------------------------------------------------- "Grd Fl HW Lp" = CIRCULATION-LOOP TYPE = HW LOOP-SIZE-RATIO = 1.15 LOOP-OPERATION = DEMAND PUMP-SCHEDULE = "Seasonal Htg Sch" DESIGN-HEAT-T = 170 HEAT-SETPT-CTRL = FIXED MAX-RESET-T = 173 MIN-RESET-T = 160 LOOP-PUMP = "Grd Fl HW Lp Pump" HEAD-SETPT = 45 LOOP-AUX-KW = 0 .. "Domestic Hot Water Loop" = CIRCULATION-LOOP TYPE = DHW DESIGN-HEAT-T = 135 PROCESS-FLOW = ( 0.0513946 ) PROCESS-SCH = ( "DHW Eqp NRes Sch" ) DHW-INLET-T = 51 .. "Bsmt HW Lp" = CIRCULATION-LOOP TYPE = HW SIZING-OPTION = SECONDARY LOOP-SIZE-RATIO = 1.1 LOOP-OPERATION = DEMAND PUMP-SCHEDULE = "Seasonal Htg Sch" DESIGN-HEAT-T = 170 LOOP-SETPT-RNG = 4 MAX-RESET-T = 173 LOOP-PUMP = "Bsmt HW Pump" .. "Top Fl HW Lp" = CIRCULATION-LOOP TYPE = HW LOOP-SIZE-RATIO = 1.15 LOOP-OPERATION = DEMAND PUMP-SCHEDULE = "Seasonal Htg Sch" DESIGN-HEAT-T = 170 LOOP-SETPT-RNG = 4 LOOP-PUMP = "Top Fl HW Lp Pump" .. $ --------------------------------------------------------- $ Chillers $ --------------------------------------------------------- $ --------------------------------------------------------- $ Boilers $ --------------------------------------------------------- "Grd Fl Lp Boiler" = BOILER TYPE = HW-BOILER CAPACITY-RATIO = 1.15 HEAT-INPUT-RATIO = 1.16279 LOCATION = ZONE ZONE-NAME = "Off Grd Fl Zn" FUEL-METER = "GFOM Grd Fl Oil Meter" AQUASTAT-SETPT-T = 170 HW-LOOP = "Grd Fl HW Lp" .. "Bsmt Lp Boiler" = BOILER TYPE = HW-BOILER CAPACITY-RATIO = 1.5 HEAT-INPUT-RATIO = 1.16279 LOCATION = ZONE ZONE-NAME = "Util Cor Bsmt Zn" FUEL-METER = "BFOM Bsmt Oil Meter" AQUASTAT-SETPT-T = 170 HW-LOOP = "Bsmt HW Lp" .. "Top Fl Lp Boiler" = BOILER TYPE = HW-BOILER CAPACITY-RATIO = 1.15 HEAT-INPUT-RATIO = 1.16279 LOCATION = ZONE ZONE-NAME = "Off Top Fl Zn" FUEL-METER = "TFOM Top Fl Oil Meter" AQUASTAT-SETPT-T = 170 HW-LOOP = "Top Fl HW Lp" .. $ --------------------------------------------------------- $ Domestic Water Heaters $ --------------------------------------------------------- "Domestic Water Heater" = DW-HEATER TYPE = ELEC TANK-VOLUME = 50 CAPACITY = 0.0195359 TANK-UA = 1.25 LOCATION = ZONE ZONE-NAME = "Util Cor Bsmt Zn" DHW-LOOP = "Domestic Hot Water Loop" .. $ --------------------------------------------------------- $ Heat Rejection $ --------------------------------------------------------- $ --------------------------------------------------------- $ Tower Free Cooling $ --------------------------------------------------------- $ --------------------------------------------------------- $ Photovoltaic Modules $ --------------------------------------------------------- $ --------------------------------------------------------- $ Electric Generators $ --------------------------------------------------------- $ --------------------------------------------------------- $ Thermal Storage $ --------------------------------------------------------- $ --------------------------------------------------------- $ Ground Loop Heat Exchangers $ --------------------------------------------------------- $ --------------------------------------------------------- $ Compliance DHW (residential dwelling units) $ --------------------------------------------------------- $ ********************************************************* $ ** ** $ ** Steam & Chilled Water Meters ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Steam Meters $ --------------------------------------------------------- $ --------------------------------------------------------- $ Chilled Water Meters $ --------------------------------------------------------- $ ********************************************************* $ ** ** $ ** HVAC Systems / Zones ** $ ** ** $ ********************************************************* SET-DEFAULT FOR SYSTEM TYPE = SZRH ERV-RECOVER-MODE = OA-HEATING .. SET-DEFAULT FOR ZONE TYPE = CONDITIONED HFLOW/AREA = 0 HW-LOOP = "Grd Fl HW Lp" BBRD-LOOP = "Grd Fl HW Lp" .. "UCB HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1 HEAT-SIZING-RATI = 1 COOL-SIZING-RATI = 0.1 MAX-SUPPLY-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" MIN-OUTSIDE-AIR = 0 RECOVER-EXHAUST = YES VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Bsmt HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "ABM" MSTR-FUEL-METER = "BFOM Bsmt Oil Meter" SOURCE-FUEL-METE = "BFOM Bsmt Oil Meter" HEAT-FUEL-METER = "BFOM Bsmt Oil Meter" COOL-FUEL-METER = "BFOM Bsmt Oil Meter" SUPP-FUEL-METER = "BFOM Bsmt Oil Meter" DHW-FUEL-METER = "BFOM Bsmt Oil Meter" CONTROL-ZONE = "Util Cor Bsmt Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 60 ERV-RUN-CTRL = WHEN-FANS-ON ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-OA-STATIC = 1.5 ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Util Cor Bsmt Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -40000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 58 EXHAUST-FLOW = 58 HMIN-FLOW/AREA = 0.06 CMIN-FLOW/AREA = 0.06 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "Bsmt Heating Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "Bsmt Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = FROM-LOADS MSTR-ELEC-METER = "ABM" HW-VALVE-TYPE = THREE-WAY HW-LOOP = "Bsmt HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Bsmt HW Lp" SPACE = "Atr Bsmt Sp" .. "Util Cor Bsmt Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 69 DESIGN-COOL-T = 71 SIZING-OPTION = FROM-LOADS MSTR-ELEC-METER = "ABM" BBRD-LOOP = "Bsmt HW Lp" SPACE = "At Bsmt Plnm" .. "NL HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 HEAT-SIZING-RATI = 1.4 COOL-SIZING-RATI = 0.1 RETURN-AIR-PATH = DIRECT MAX-SUPPLY-T = 120 HEAT-SET-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" RECOVER-EXHAUST = NO VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*2*2.5*5/2304} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Grd Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "NLM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" LIGHT-ELEC-METER = "NLM" TASK-ELEC-METER = "NLM" EQUIP-ELEC-METER = "NLM" SOURCE-ELEC-METE = "NLM" HEAT-ELEC-METER = "NLM" COOL-ELEC-METER = "NLM" HTREJ-ELEC-METER = "NLM" AUX-ELEC-METER = "NLM" VENT-ELEC-METER = "NLM" REFG-ELEC-METER = "NLM" SUPP-ELEC-METER = "NLM" DHW-ELEC-METER = "NLM" HEAT-FUEL-METER = "GFOM Grd Fl Oil Meter" CONTROL-ZONE = "N Lab Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = NONE ERV-PREHEAT-CTRL = RESET-SETPT .. "N Lab Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -7000 FLOW/AREA = 0 OA-FLOW/PER = 0 OUTSIDE-AIR-FLOW = 0 EXHAUST-FLOW = 0 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "N Lab Htg Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "N Lab Clg Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "NLM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" SOURCE-FUEL-METE = "GFOM Grd Fl Oil Meter" HEAT-FUEL-METER = "GFOM Grd Fl Oil Meter" COOL-FUEL-METER = "GFOM Grd Fl Oil Meter" SUPP-FUEL-METER = "GFOM Grd Fl Oil Meter" DHW-FUEL-METER = "GFOM Grd Fl Oil Meter" MIN-FLOW-SOURCE = COLD-DUCT HW-LOOP = "Grd Fl HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Grd Fl HW Lp" SPACE = "N Lab Spc" .. "SL HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 HEAT-SIZING-RATI = 1 COOL-SIZING-RATI = 0.1 RETURN-AIR-PATH = DIRECT MAX-SUPPLY-T = 120 HEAT-SET-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" RECOVER-EXHAUST = NO VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*7*3*5/2304} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Top Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "NLM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" LIGHT-ELEC-METER = "NLM" TASK-ELEC-METER = "NLM" EQUIP-ELEC-METER = "NLM" SOURCE-ELEC-METE = "NLM" HEAT-ELEC-METER = "NLM" COOL-ELEC-METER = "NLM" HTREJ-ELEC-METER = "NLM" AUX-ELEC-METER = "NLM" VENT-ELEC-METER = "NLM" REFG-ELEC-METER = "NLM" SUPP-ELEC-METER = "NLM" DHW-ELEC-METER = "NLM" HEAT-FUEL-METER = "GFOM Grd Fl Oil Meter" CONTROL-ZONE = "S Lab Zn" ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = NONE ERV-PREHEAT-CTRL = RESET-SETPT .. "S Lab Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -30000 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "S Lab Htg Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "S Lab Clg Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "SLM" MIN-FLOW-SOURCE = COLD-DUCT HW-LOOP = "Top Fl HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Top Fl HW Lp" SPACE = "S Lab Spc" .. "S Lab Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 68 DESIGN-COOL-T = 72 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "SLM" BBRD-LOOP = "Top Fl HW Lp" SPACE = "S Lab Pln Spc" .. "OB HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1 HEAT-SIZING-RATI = 1 COOL-SIZING-RATI = 0.1 RETURN-AIR-PATH = PLENUM-ZONES MAX-SUPPLY-T = 120 HEAT-SET-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" RECOVER-EXHAUST = YES VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Grd Fl HW Lp" COOLING-CAPACITY = 0 HEATING-CAPACITY = 0 MSTR-ELEC-METER = "OBM" MSTR-FUEL-METER = "BFOM Bsmt Oil Meter" LIGHT-ELEC-METER = "OBM" TASK-ELEC-METER = "OBM" EQUIP-ELEC-METER = "OBM" SOURCE-ELEC-METE = "OBM" HEAT-ELEC-METER = "OBM" COOL-ELEC-METER = "OBM" HTREJ-ELEC-METER = "OBM" AUX-ELEC-METER = "OBM" VENT-ELEC-METER = "OBM" REFG-ELEC-METER = "OBM" SUPP-ELEC-METER = "OBM" DHW-ELEC-METER = "OBM" HEAT-FUEL-METER = "BFOM Bsmt Oil Meter" COOL-FUEL-METER = "BFOM Bsmt Oil Meter" CONTROL-ZONE = "Off Bsmt Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 120 ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Off Bsmt Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 69 DESIGN-COOL-T = 70 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "OBM" SPACE = "Off Bsmt Pln Spc" .. "Off Bsmt Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -30000 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 120 EXHAUST-FLOW = 120 HMIN-FLOW/AREA = 0.06 CMIN-FLOW/AREA = 0.06 DESIGN-HEAT-T = 65 HEAT-TEMP-SCH = "Bsmt Heating Sch" DESIGN-COOL-T = 75 COOL-TEMP-SCH = "Bsmt Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = FROM-LOADS MSTR-ELEC-METER = "OBM" HW-VALVE-TYPE = THREE-WAY HW-LOOP = "Bsmt HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Bsmt HW Lp" SPACE = "Off Bsmt Spc" .. "OTF HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 COOL-SIZING-RATI = 0.1 MAX-SUPPLY-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" SUPPLY-FLOW = 138 RETURN-FLOW = 138 RECOVER-EXHAUST = YES VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*11*2.5*5/2016} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Top Fl HW Lp" COOLING-CAPACITY = 0 CONTROL-ZONE = "Off Top Fl Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 138 ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Off Top Fl Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -90000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 121 EXHAUST-FLOW = 121 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "Up Off Zns Heating Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "Up Off Zns Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "OTM" MSTR-FUEL-METER = "TFOM Top Fl Oil Meter" MIN-FLOW-SOURCE = COLD-DUCT HW-LOOP = "Top Fl HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Top Fl HW Lp" SPACE = "Off Top Flr Spc" OA-FLOW/AREA = 0.06 .. "Off Top Fl Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 66 DESIGN-COOL-T = 74 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "OTM" MSTR-FUEL-METER = "TFOM Top Fl Oil Meter" SPACE = "Off TF Pln Spc" .. "AT HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 COOL-SIZING-RATI = 0.1 MAX-SUPPLY-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" RECOVER-EXHAUST = YES VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*4*2.5*5/1064} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Top Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "ATM" MSTR-FUEL-METER = "TFOM Top Fl Oil Meter" CONTROL-ZONE = "Atrium Zone" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 60 ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Atrium Zone" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -21000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 60 EXHAUST-FLOW = 60 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "Atr Htg Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "Up Off Zns Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "ATM" MIN-FLOW-SOURCE = COLD-DUCT HW-LOOP = "Top Fl HW Lp" BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Top Fl HW Lp" SPACE = "Atrium Sp" .. "OGF HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 COOL-SIZING-RATI = 0.1 MAX-SUPPLY-T = 120 HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" SUPPLY-FLOW = 121 RECOVER-EXHAUST = YES VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*8*2.5*5/2016} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Grd Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "OGM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" CONTROL-ZONE = "Off Grd Fl Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 120 ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Off Grd Fl Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -90000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 120 ASSIGNED-FLOW = 0 EXHAUST-FLOW = 120 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "Up Off Zns Heating Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "Up Off Zns Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 4 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "OGM" MIN-FLOW-SOURCE = COLD-DUCT BBRD-VALVE-TYPE = THREE-WAY SPACE = "Off Grd Flr Spc" .. "Off Grd Fl Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 66 DESIGN-COOL-T = 74 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "OGM" SPACE = "Off GF Pln Spc" .. "GFH HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1.15 COOL-SIZING-RATI = 0.1 RETURN-AIR-PATH = PLENUM-ZONES HEATING-SCHEDULE = "Seasonal Htg Sch" COOLING-SCHEDULE = "Seasonal Clg Sch" RECOVER-EXHAUST = YES VENT-METHOD = S-G VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FRAC-VENT-AREA = {0.6*1*2.5*5/1015} NATURAL-VENT-SCH = "Nat Vent Sch" OPEN-VENT-SCH = "Win Open Prob Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Grd Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "AGM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" CONTROL-ZONE = "Atr Hallway Grd Fl Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 60 ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Atr Hallway Grd Fl Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -20000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 58 EXHAUST-FLOW = 58 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "Up Off Zns Heating Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "Up Off Zns Cooling Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "AGM" MIN-FLOW-SOURCE = COLD-DUCT BBRD-VALVE-TYPE = THREE-WAY SPACE = "At Grd Fl Sp" OA-FLOW/AREA = 0.06 .. "Atr Hallway Grd Fl Pln Zn" = ZONE TYPE = PLENUM DESIGN-HEAT-T = 66 DESIGN-COOL-T = 74 SIZING-OPTION = ADJUST-LOADS MSTR-ELEC-METER = "AGM" SPACE = "At Grd Fl Pln Sp" .. "ES HVAC Sys" = SYSTEM TYPE = PSZ HEAT-SOURCE = HOT-WATER BASEBOARD-SOURCE = HOT-WATER SIZING-RATIO = 1 COOL-SIZING-RATI = 0.1 HEATING-SCHEDULE = "Seasonal Htg Sch" RECOVER-EXHAUST = YES VENT-TEMP-SCH = "Nat Vent Desired Temp Sch" FAN-SCHEDULE = "All Fans Sch" FAN-CONTROL = SPEED SUPPLY-STATIC = 0.5 RETURN-STATIC = 0.2 NIGHT-CYCLE-CTRL = CYCLE-ON-FIRST NIGHT-VENT-CTRL = NOT-AVAILABLE INDOOR-FAN-MODE = CONTINUOUS HW-LOOP = "Grd Fl HW Lp" COOLING-CAPACITY = 0 MSTR-ELEC-METER = "ESM" MSTR-FUEL-METER = "GFOM Grd Fl Oil Meter" CONTROL-ZONE = "Elev Shaft Zn" ERV-RECOVER-TYPE = SENSIBLE-HX ERV-OA-FLOW = 20 ERV-RUN-CTRL = WHEN-FANS-ON ERV-TEMP-CTRL = FLOAT ERV-MOTOR-CLASS = PREMIUM ERV-FROST-CTRL = PREHEAT-OA ERV-PREHEAT-CTRL = RESET-SETPT .. "Elev Shaft Zn" = ZONE TYPE = CONDITIONED MIN-FLOW-RATIO = 0 BASEBOARD-RATING = -8000 FLOW/AREA = 0.06 OA-FLOW/PER = 5 OUTSIDE-AIR-FLOW = 16 EXHAUST-FLOW = 16 DESIGN-HEAT-T = 66 HEAT-TEMP-SCH = "El Sh Htg Sch" DESIGN-COOL-T = 74 COOL-TEMP-SCH = "El Sh Clg Sch" BASEBOARD-CTRL = THERMOSTATIC THERMOSTAT-TYPE = TWO-POSITION THROTTLING-RANGE = 8 SIZING-OPTION = FROM-LOADS MSTR-ELEC-METER = "ESM" MIN-FLOW-SOURCE = COLD-DUCT BBRD-VALVE-TYPE = THREE-WAY BBRD-LOOP = "Grd Fl HW Lp" SPACE = "Elev Shaft Sp" .. $ ********************************************************* $ ** ** $ ** Metering & Misc HVAC ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Equipment Controls $ --------------------------------------------------------- $ --------------------------------------------------------- $ Load Management $ --------------------------------------------------------- $ ********************************************************* $ ** ** $ ** Utility Rates ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Ratchets $ --------------------------------------------------------- $ --------------------------------------------------------- $ Block Charges $ --------------------------------------------------------- "GVEA Block Energy Chg" = BLOCK-CHARGE BLOCKS-ARE = CUMULATIVE BLOCKS-1 = ( 15000, 100000 ) COSTS-1 = ( 0.11925, 0.09928 ) .. $ --------------------------------------------------------- $ Utility Rates $ --------------------------------------------------------- "GVEA Gen Serv 2(1)" = UTILITY-RATE TYPE = ELECTRICITY ELEC-METERS = ( "EM1" ) DEMAND-CHGS = ( 7.98 ) DEMAND-WINDOW = FIXED BLOCK-CHARGES = ( "GVEA Block Energy Chg" ) ESCALATION = 10 MIN-MON-CHGS = ( 50 ) MIN-MON-DEM-CHGS = ( 0 ) UNIT-TAX-BLOCKS = ( 100000 ) UNIT-TAXES = ( 0.000433 ) .. "Fuel Oil Rate" = UTILITY-RATE TYPE = FUEL-OIL FUEL-METERS = ( "FM1", "BFOM Bsmt Oil Meter", "GFOM Grd Fl Oil Meter", "TFOM Top Fl Oil Meter" ) ENERGY-CHG = 2.5 ESCALATION = 15 .. $ ********************************************************* $ ** ** $ ** Output Reporting ** $ ** ** $ ********************************************************* $ --------------------------------------------------------- $ Loads Non-Hourly Reporting $ --------------------------------------------------------- LOADS-REPORT VERIFICATION = ( ALL-VERIFICATION ) SUMMARY = ( ALL-SUMMARY ) REPORT-FREQUENCY = HOURLY .. $ --------------------------------------------------------- $ Systems Non-Hourly Reporting $ --------------------------------------------------------- SYSTEMS-REPORT VERIFICATION = ( ALL-VERIFICATION ) SUMMARY = ( ALL-SUMMARY ) .. $ --------------------------------------------------------- $ Plant Non-Hourly Reporting $ --------------------------------------------------------- PLANT-REPORT VERIFICATION = ( ALL-VERIFICATION ) SUMMARY = ( ALL-SUMMARY ) .. $ --------------------------------------------------------- $ Economics Non-Hourly Reporting $ --------------------------------------------------------- ECONOMICS-REPORT VERIFICATION = ( ALL-VERIFICATION ) SUMMARY = ( ALL-SUMMARY ) .. $ --------------------------------------------------------- $ Hourly Reporting $ --------------------------------------------------------- "Hourly Rpt (elec/gas totals)" = HOURLY-REPORT LIBRARY-ENTRY "Hourly Rpt (elec/gas totals)" .. "Hourly Rpt (elec ltg & msc)" = HOURLY-REPORT LIBRARY-ENTRY "Hourly Rpt (elec ltg & msc)" .. "Elec/Fuel 1-Mtr HVAC Hrly Rpt" = HOURLY-REPORT LIBRARY-ENTRY "Elec/Fuel 1-Mtr HVAC Hrly Rpt" .. $ --------------------------------------------------------- $ THE END $ --------------------------------------------------------- END .. COMPUTE .. STOP ..